Wall-mounted storage batteries are easy to buy badly. The nameplate says 100Ah, the marketing rounds that into "5kWh", and the buyer's actual question — will it run my house through the evening, the night, or an outage? — gets answered by nobody. Sizing is not complicated, but it has to start from the load and work through the real figures on the unit's specification table. This guide works the example with the range's anchor unit: a 51.2V 100Ah wall-mounted LiFePO4 battery rated at 5.12kWh, rated ≥6000 cycles at 0.5C, 90% depth of discharge and ≥80% capacity retained.
Step one: the daily load you actually want to cover
Write down what the battery is for. Backup for critical loads — lights, fridge, router, a few sockets — might total 2–3kWh across an outage evening. Shifting a whole household's evening consumption off peak tariff is a bigger number, often 5–10kWh. Solar self-consumption sits between: store the midday surplus, spend it after dark. The honest figure is the energy, in kWh, of the loads you intend to run and the hours you intend to run them. Everything else in sizing is arithmetic on that number.
Step two: usable energy is nameplate times depth of discharge
The anchor unit's nameplate energy is 5.12kWh, and its cycle-life rating — 6000 cycles or more — is specified at 0.5C and 90% depth of discharge, with at least 80% of capacity retained at the end of it. That pairing is the honest way to size: plan on roughly 4.6kWh of usable energy per unit per cycle if you want the rated cycle life, not the full 5.12kWh. A unit cycled daily at that depth is rated for well over a decade of cycles. Buyers comparing units should insist on the same pairing from every quote: a cycle-life figure with no stated depth of discharge and rate is not comparable, and a usable-energy figure with no stated depth is not either. This unit states both, which is the standard to hold the alternatives to.
Step three: check the power, not just the energy
Energy decides how long; current decides what. The anchor unit discharges at 100A continuous (120A maximum for up to three minutes) against a maximum load of 5kW, and charges at 50A standard, 100A maximum. That covers typical household evening loads comfortably — lighting, refrigeration, entertainment, cooking appliances used one or two at a time — but a home that wants to run several heavy appliances simultaneously, or charge the battery very fast from a large solar array, needs the parallel calculation in the next step, or a different unit. Match the battery's figures against the inverter you intend to pair it with, and against the inverter's surge behaviour for motor loads; the unit's working range is 57.6–44.8V, and the inverter's charge ceiling must sit inside it.
Step four: scale with parallel units, on one platform
The unit supports up to 16 in parallel, which takes the same installation from 5.12kWh nameplate to 81.92kWh without changing platform, wiring concept or communication. Practically: two units give 10.24kWh nameplate and about 9.2kWh usable at 90% depth, with a combined 200A continuous discharge ceiling; three units cover most whole-house evening-shift duties; sixteen units, at about 43kg each, are about 688kg of battery — a floor-standing installation planned as one from the start. Communication is on the unit — RS485, CAN and RS232 — so the inverter conversation is a specification question to settle before purchase, not a surprise after it. Physically, each unit is 145×360×530mm and about 43kg: plan the wall or floor space for the final count, not the first.
Step five: 100Ah or 200Ah?
The same wall format also runs to 51.2V 200Ah. The 100Ah unit is the anchor — parallel scaling, the 6000-cycle rating at stated conditions. The 200Ah point halves the unit count for the same energy (two 100Ah units in parallel deliver the same 10.24kWh nameplate in two enclosures with two fixing patterns and the option to install one now and double later; a single 200Ah-class unit concentrates it in one enclosure and one heavier lift) and suits installations where wall positions are scarce. The arithmetic shows no electrical winner at equal energy; the deciding questions are logistical — wall positions, staged purchase, and whether the outage plan prefers two independent units, one of which can be serviced while the other carries the essentials. Where the choice matters, send the target energy, the inverter model and the daily cycle pattern with the enquiry and have the comparison made on the data.
Communication, mounting and the two-unit example
Two practicalities close the sizing job. First, communication: the anchor unit carries RS485, CAN and RS232 ports, which is what lets the inverter charge and discharge it intelligently and report its state of charge. Confirm the inverter speaks one of the three before ordering, especially in parallel sets, where the units and the inverter must agree on who is in charge. Second, the physical install: at about 43kg a unit is a two-person lift, and a wall carrying three of them is carrying about 129kg plus brackets — check the wall, or floor-stand the set. The unit is rated IP20 with natural cooling: an indoor unit, sited where air moves. Worked through, the common two-unit case looks like this: 10.24kWh nameplate, about 9.2kWh usable at the rated 90% depth, and a combined 200A continuous discharge ceiling against the 5kW-per-unit maximum load. That combination covers the typical brief of "evening loads plus overnight essentials" for most households, with the parallel path still open to sixteen units if the brief grows.
Charging the unit, and smaller installations
The unit's working range tops out at 57.6V, so the inverter or charger paired with it must be a 51.2V-class (16S) unit set to that ceiling — not a charger chosen by a nominal "48V" label, since the storage family's nominal is 51.2V and the ceiling follows from the range, not from the class nickname. The charge rates translate directly into solar terms: 50A standard at the 51.2V class is roughly 2.5kW of charging power, and the 100A maximum about 5kW, so an array of about 3kW charges the unit through a good solar day while the house runs. At the smaller end, the same load-first method scales down: below the wall scale, the catalogue's 12.8V 200Ah battery serves the small-storage briefs the 51.2V family is too large for — the garden office with 2kWh of evening load, the caravan or boat whose systems are already 12V, the shed with a freezer and lights. Its 2.56kWh and 2.4kW maximum load fit those duties natively and its roughly 23kg travels; its extension (series and parallel, to a maximum of 8 in series) lets a 12V-native installation stay 12V. Small storage punishes over-buying more than under-buying, because the unused capacity still cycles its calendar away on the shelf.
Three more worked houses
The smallholding. Loads: house evening base 3.0kWh, a well pump drawing 1.1kW for an hour daily (1.1kWh), workshop tools intermittently 2kW. The pump is the sizing fact: its 1.1kW run must sit inside the battery's 5kW-per-unit maximum load, which one unit manages and two units make comfortable. Energy: 4.1kWh of shiftable load fits one unit's 4.6kWh usable figure with the workshop on the grid; the two-unit answer (9.2kWh usable) takes the workshop's evening use off peak as well. The coastal house with outages. The brief changes from tariff to continuity: keep refrigeration (0.6kWh/day), lighting and communications (0.5kWh) and a router shelf alive for 48 hours without grid. Essential energy is about 2.2kWh across the two days — well inside one unit — and everything essential at once is under 1kW, so one unit is the honest specification, and the second unit's money is better spent on the changeover arrangement that makes the outage case automatic. The workshop flat. Evening loads 2.8kWh, but noise rules push the washing machine and water heating into the stored-energy window: add 2.2kWh, total 5.0kWh — just past one unit's usable figure, the classic two-unit answer, and the worked example shows why the second unit so often follows the first within a year: the brief grew by one appliance.
When the wall is the wrong shape: rack and stacked
Some buildings refuse wall batteries: rented walls that may not be drilled, plant rooms floored with equipment, cabinets that already exist. The catalogue's other formats answer the same electrical brief in different shapes. Rack-mounted storage suits the property with a 19-inch cabinet culture — telecom rooms, control rooms, workshops with racked equipment — where frontal service access and shelved modules match how the building is already maintained. Stacked storage suits the floor-standing case: modules piled on a base, no wall fixings, capacity added upward, the format for basements and plant rooms with more floor than wall. The electrical discipline does not change with the shape — 51.2V nominal class, inverter ceiling inside the range, the communication options — which is the real content of the format decision: it is a building decision wearing an electrical costume, and buyers should make it with the building's constraints stated first. The storage hub page walks the formats side by side.
What this specification does not tell you — and to ask anyway
A specification's silences are part of its content. On this unit the stated set runs to voltage window, charge pair, discharge pair with its three-minute maximum, protocol trio, mass, envelope, IP20 rating with natural cooling, a 36-month warranty, a sixteen-unit parallel ceiling and a cycle rating with its rate, depth and retained-capacity conditions — and the figures to ask for at enquiry are the seasonal ones: standby consumption and self-discharge across a season, the pair that decides a bank idling through a holiday month. The habit generalises beyond this model: the suppliers worth buying from answer silence-questions with numbers rather than with reassurance.
The storage numbers on one page
Wall unit: 51.2V nominal, 100Ah, 5.12kWh nameplate, about 4.6kWh usable at nine-tenths depth, working range 57.6–44.8V, charge 50A standard and 100A maximum, discharge 100A continuous and 120A maximum (≤3 min), maximum load 5kW, ≥6000 cycles at 0.5C / 90% DOD / ≥80% retained, RS485, RS232 and CAN, IP20, natural cooling, about 43kg, 145×360×530mm, parallel ceiling sixteen units, warranty 36 months. Bank ladder: two units 10.24kWh and about 9.2kWh usable; three units 15.36kWh; four 20.48kWh; sixteen 81.92kWh. Sister format points: the 51.2V 200Ah point at 10.24kWh in a single enclosure class; rack and stacked formats on the same 51.2V discipline. The 12V shelf: 12.8V, 200Ah, 2.56kWh, 14.6V charge ceiling, 200A continuous, 450A peak, about 23kg, series/parallel extension to 8 in series. Worked evening used throughout: 4.2kWh of shiftable load and a 2.2kW coincident peak for the four-person house; essentials floor 2.2kWh across a 48-hour outage for the coastal case. The numbers are the guide; everything else in it is commentary.
The last word. Size from measured evenings, not from appliance brochures: the meter's half-hour data, one plug meter, and an honest essentials list will choose between one unit and two more reliably than any advertisement — and the wall will hold whichever answer the arithmetic returns.
Cycle-life economics: what 6000 cycles is worth
The anchor unit's rating — ≥6000 cycles at 0.5C, 90% depth of discharge, ≥80% capacity retained — can be turned into the only currency that matters: lifetime energy. At about 4.6kWh usable per cycle, 6000 cycles is roughly 27.6 megawatt-hours of delivered energy across the unit's life. A household cycling daily spends that rating in about sixteen years; a household cycling only on solar days, perhaps 250 cycles a year, spends it in twenty-four. Against that figure the purchase price divides into a cost per megawatt-hour that buyers can compare across any quotes willing to state their own conditions — and the comparison discipline is the conditions, not the headline: a rival's 6000 cycles at 50% depth delivers half the lifetime energy of this unit's 6000 at 90%, and a rating with no stated depth is not a rating at all. This is why the sizing method in this guide keeps returning to the same habit: never compare a number, compare a number with its conditions attached.
The inverter conversation, in detail
The unit carries three communication ports — RS485, CAN and RS232 — and the trio is worth understanding before the inverter is chosen, because the conversation determines how intelligently the system behaves. With a live data link, the inverter charges against the battery's own reported state of charge, respects its current limits dynamically, and logs the history that warranty and expansion decisions later need. Without one, the inverter works from voltage thresholds alone: it will still charge and discharge the battery, but blind — cutting off early or late by chemistry's voltage curve rather than by the battery's knowledge of itself. The practical sequence: choose the battery bank size from the load arithmetic in this guide; choose the inverter for the house's peak load and the array; then confirm, in writing, which of the three protocols the pair will speak and who commissions the settings — the 57.6V ceiling and the 50A standard / 100A maximum charge pair among them. In parallel banks the question sharpens, because the units and the inverter must agree on a master; it is a commissioning line item, priced once, and the installations that skip it are the ones that behave oddly in month two.
An expansion diary: year one to year three
Most wall installations in this pattern grow, and the parallel ceiling of sixteen units exists so the growth never strands the first purchase. Year one: one unit, 5.12kWh nameplate, the essentials-plus-evening brief — the meter data says the house shifts 4.2kWh, the unit's usable figure is about 4.6kWh, the fit is exact and slightly uncomfortable. Year two: a heat pump or an electric vehicle arrives, the evening brief grows by 3kWh, and the second unit goes on the same wall — 10.24kWh nameplate, about 9.2kWh usable, the bank's combined discharge ceiling now 200A — with no change of inverter family, no change of platform, and the first unit's history intact in the same monitoring conversation. Year three: the question is no longer capacity but shape — a third unit on the wall (about 129kg of batteries plus brackets, the wall checked before the order), or the same electrical brief re-homed into the rack or stacked formats the storage hub describes. The diary's moral is the sizing method's: buy the first unit for the measured brief, and buy the platform for the brief's growth.
Siting in practice: IP20, natural cooling and the honest room
Two specification lines govern where this unit may live, and both are commonly misread as formalities. IP20 means protection against fingers and nothing against water: the unit is an indoor product, and "indoor" means a roof, dry air and no hose-downs — a garage, utility room or plant room qualifies; a carport wall, however sheltered it feels, is a negotiation the rating does not support. Natural cooling means the case sheds heat to the room air: the unit needs clearance as the installation instructions state, not a sealed cabinet, and a bank of four in a small room is a ventilation question as well as an electrical one — 20.48kWh of batteries working at a combined 400A ceiling in summer is a heat source with a planning figure. Neither line is a defect; both are the difference between a battery installed to its specification and one installed to its photograph. The installers who last are the ones who read the two lines aloud to the customer before the drill comes out.
Questions buyers actually ask about this unit
Can it run the whole house? Energy first: the essentials-plus-evening brief fits one unit; the whole-house brief, with simultaneous heavy appliances, is a two-to-four-unit bank and an inverter sized to the peak — the bank's combined current ceiling (200A at two units) and the 5kW-per-unit load figure are the two numbers the installer works from. What happens in a long outage? The essentials floor in the worked example — refrigeration, lighting, communications — is about 2.2kWh across 48 hours, inside one unit's usable figure with the discipline of not running discretionary loads. Can I add units later? Yes, to sixteen in parallel, on the same platform; banks are commissioned as sets, so the expansion visit includes the settings check, not just the bolting. Does it need the internet or an app? The unit's conversation is with the inverter, over RS485, CAN or RS232; monitoring arrangements ride on that link and are an inverter-side choice. What should my first message contain? The evening energy from the meter, the coincident peak, the inverter model or shortlist, the room the batteries will live in, and the growth you already suspect — five facts that turn this guide into a quotation.
The rack and stacked formats, in the family's own numbers
The storage family runs wider than the wall: rack-mounted, stacked and wall-mounted LiFePO4 systems in a 51.2V class spanning 100–600Ah. In energy terms that span is roughly 5kWh to 30kWh per unit line — the territory between the single wall unit and the small commercial installation. The rack format answers the cabinet building: modules shelved in a frame, frontal access, the plant-room pattern. The stacked format answers the floor: modules piled on a base, capacity growing upward, no wall fixings — the basement and outbuilding pattern. Both formats inherit the family's discipline rather than the wall unit's specific table: 51.2V nominal class, a working range the inverter must respect, communication as a specification question. Buyers whose brief outgrows the wall should read the storage hub's format walk before assuming a bigger wall unit exists — in this family, growth changes shape before it changes size, and the shape decision is the building's, made once.
Reading a meter: the measurement week
The sizing method in this guide stands on one input — the household's real evening energy — and the measurement deserves its own paragraph because it is where most installations go wrong. The best source is the smart meter's half-hourly data: export a fortnight, find the window the battery would serve (typically the hours between the solar decline and the late evening), and average the energy inside it across ordinary days, ignoring the party and the holiday. The second-best source is a plug meter on the circuits that matter for a week. The worst source is the appliance nameplate sum, which overstates everything by assuming coincidence that never happens. Two numbers come out of the exercise: the energy (which chooses between one unit and two) and the coincident peak (which checks against the 5kW-per-unit load figure). A fortnight's patience at this stage is worth more than any single specification on any page in the catalogue, this one included.
What a proper quotation should itemise
Close the guide with the document that ends the process: the quotation itself, and what a buyer should expect it to itemise for a wall-battery installation. The units, by their specification — 51.2V 100Ah, with the figures restated rather than paraphrased. The inverter pairing, with the protocol the pair will speak and the settings it will be commissioned to: the 57.6V ceiling, the charge pair, the discharge pair. The mounting: wall fixings rated for about 43kg per unit, or the floor stand, named. The communications commissioning, as a line, not an assumption. The warranty — 36 months for this model — with its start condition. And the expansion terms: the per-unit price held for a stated period, because the parallel path to sixteen units is part of what is being bought. A quotation that itemises those six things can be compared against any rival's; one that offers a single lump sum and a photograph cannot, and the difference is the entire argument of this guide restated as paperwork.
The 12V shelf revisited: when small storage is the honest answer
Not every storage brief deserves a 51.2V platform, and the catalogue's 12.8V 200Ah battery exists for the ones that do not. Its figures: 2.56kWh, a 14.6V ceiling, 200A continuous and 450A peak discharge, a 100A standard and 200A maximum charge pair, 3000-plus cycles, a −20~60°C discharge window, Bluetooth and RS-485 options, series/parallel extension to a maximum of 8 in series, about 23kg. Read against the wall unit's method, the same sizing questions apply at the smaller scale: the evening energy (a garden office, a boat, a cabin rarely exceeds 2kWh of honest brief), the coincident peak (inside the 2.4kW maximum load), the platform question (a 12V-native installation stays 12V, and the extension path lets it grow without re-platforming). The mistake this shelf prevents is asymmetrical: over-buying small storage wastes more, proportionally, than over-buying large, because the unused capacity still ages on the shelf while the money could have bought the second battery the brief actually needed.
Three quotations, compared on one page
The comparison compresses into a single exercise: three competing quotations for the four-person house, scored against the anchor unit's conditions. Quotation A offers 5kWh and "6000 cycles" with no depth or rate attached — unscorable, and scored as such. Quotation B offers 4.8kWh usable at 80% depth with a 4000-cycle rating at that depth: lifetime energy about 19.2MWh, honestly stated, directly comparable. Quotation C is the anchor itself: about 4.6kWh usable at 90% depth, ≥6000 cycles at 0.5C with ≥80% retained — lifetime energy roughly 27.6MWh. The exercise takes ten minutes and requires nothing but the quotations' own text; its power is that two of the three documents usually cannot complete it, and a buyer learns more from the incompletion than from any figure printed in colour. Ask for the conditions; the answers, or their absence, are the comparison.
Replacement and second life, planned at purchase
A battery bank bought on a sixteen-year cycle calendar raises a question most guides skip: what happens at the end, and who decided? The planning answers belong in the purchase file. The bank's modular shape — identical units, added across years — means replacement is also modular: units are retired and replaced individually as their resistance and capacity stories diverge, rather than the bank dying as a monolith, and the commissioning baseline (a resistance reading per unit, a capacity note) is what makes the divergence visible. The retired units' route — the supplier's or the region's battery recycling channel, documented under the transport rules that govern lithium batteries — is arranged before it is needed, because a 43kg unit in a garage corner is a storage problem nobody budgeted. None of this is sentiment; it is the last page of the same arithmetic that sized the bank, and the installations that include it are the ones whose year-fifteen conversation is a purchase order rather than a problem.
The growth ceiling as a design tool
End where the sizing began, with the number sixteen. A parallel ceiling is usually read as a limit; read it instead as the platform's promise about the future — that the installation's tenth year can be served by the first year's product, purchased again, commissioned into the same conversation, and monitored on the same screen. The practical consequences belong in the first purchase: the wall or floor planned for the bank the brief might become (sixteen units are about 688kg — a floor installation, planned as one), the inverter headroom conversation held early, and the per-unit price for expansion asked while the first order gives the buyer leverage. Houses change slowly and then suddenly — a vehicle, a heat pump, a workshop — and a storage platform whose growth is a purchase order rather than a rebuild is the difference between an asset and an appliance. Size the first unit from the meter; size the platform from the imagination; both numbers are on the table, and this guide has tried to show its working for each.
The commissioning record: five numbers in a drawer
Every installation in this guide's pattern should leave one sheet of paper behind, and its contents are worth listing because they are the difference between a bank that can be serviced in year nine and one that must be reverse-engineered. One: the charge ceiling as commissioned — 57.6V, or the figure the inverter was actually set to. Two: the charge and discharge current limits as set, against the pairs (50A standard and 100A maximum; 100A continuous and 120A maximum). Three: the protocol in use and which unit is master in a parallel bank. Four: a per-unit baseline — serial, open-circuit voltage, and an internal-resistance reading against the ≤80mΩ line — taken on the day of commissioning. Five: the room's particulars — mounting, clearance, and the expansion space reserved. Five numbers and a paragraph, kept with the house's documents. The bank will outlive the installer's memory and possibly the installer; the sheet is how it introduces itself to whoever comes next.
A word about photographs and showrooms
A closing caution that costs nothing and saves much: judge a storage battery by its documents, not by its imagery. A handsome installation photograph proves that somebody, somewhere, mounted a unit handsomely; it says nothing about the ceiling the inverter was set to, the protocol the bank speaks, or the resistance baseline in the commissioning drawer. This guide's pages are illustrated with drawings and let the tables carry the persuasion — an unfashionable choice that this entire sizing method quietly depends on, because every number used here is a model's own rated figure. Buyers should extend the same courtesy in reverse: the supplier whose evidence is a table can be checked, and the checking is the relationship. Everything else is decoration, and decoration has never yet carried a house through a winter night.